⚡ Interactive Variable Frequency Drive (VFD) Simulation
AC Supply → Rectifier → DC Link → PWM Inverter → 3-Phase Induction Motor
1. VFD Power Conversion
AC SUPPLY
400 V / 60 Hz
→
RECTIFIER
AC → DC
→
DC LINK
540 V DC
→
PWM INVERTER
4 kHz
→
3-PHASE MOTOR
Induction Motor
→
MECHANICAL LOAD
50%
2. VFD Controls
READY — Press START to run the motor
3. Real-Time Motor Measurements
Frequency
0
Hz
VFD Voltage
0
V RMS
Motor Speed
0
rpm
Synchronous Speed
0
rpm
Slip
0
%
Motor Current
0
A
Torque
0
N·m
Power
0
kW
V/f Ratio
0
V/Hz
4. Motor Speed Demonstration
3-PHASE
INDUCTION
MOTOR
INDUCTION
MOTOR
Increase the VFD frequency and observe the motor/fan speed increase.
5. V/f Control Demonstration
V/f = Motor Voltage ÷ Output Frequency
Below the base frequency, the VFD approximately maintains a constant voltage-to-frequency ratio.
Below the base frequency, the VFD approximately maintains a constant voltage-to-frequency ratio.
Output Frequency
30
Hz
Output Voltage
200
V
V/f Ratio
6.67
V/Hz
Base Frequency
60
Hz
6. Oscilloscope — VFD Waveforms
Input AC Supply
Rectified DC
PWM Inverter Output
Motor Fundamental Voltage
7. PWM Demonstration
The VFD compares a sinusoidal reference with a high-frequency carrier to generate Pulse Width Modulation (PWM).
Sine Reference + Triangular Carrier
PWM Switching Pattern
PWM switching frequency:
4 kHz
8. VFD Harmonics Demonstration
The harmonic display is an educational visualization rather than a measurement of a particular commercial VFD.
9. Load and Slip Demonstration
For a 4-pole motor, synchronous speed is approximately:
Ns = 120 × f / P
Where: Ns = synchronous speed (rpm)
f = frequency (Hz)
P = number of poles = 4
Where: Ns = synchronous speed (rpm)
f = frequency (Hz)
P = number of poles = 4
| Frequency | Synchronous Speed | Illustrative Motor Speed* |
|---|---|---|
| 10 Hz | 300 rpm | ≈ 285 rpm |
| 20 Hz | 600 rpm | ≈ 570 rpm |
| 30 Hz | 900 rpm | ≈ 855 rpm |
| 40 Hz | 1,200 rpm | ≈ 1,140 rpm |
| 50 Hz | 1,500 rpm | ≈ 1,425 rpm |
| 60 Hz | 1,800 rpm | ≈ 1,710 rpm |
*Illustrative values. Actual induction-motor speed depends on motor design, load and slip.
10. VFD Fault Demonstration
Try this experiment:
1. Select Motor Overload.
2. Press START.
3. Increase the load toward 100%.
4. Observe motor current, speed and the fault status.
The fault behavior here is simplified for educational demonstration and does not represent the protection settings of a particular VFD.
1. Select Motor Overload.
2. Press START.
3. Increase the load toward 100%.
4. Observe motor current, speed and the fault status.
The fault behavior here is simplified for educational demonstration and does not represent the protection settings of a particular VFD.
11. Suggested Virtual Laboratory Experiment
- Set the frequency to 10 Hz and start the motor.
- Gradually increase the frequency to 60 Hz.
- Observe motor speed and V/f ratio.
- Increase the motor load from 20% to 100%.
- Observe current, torque, speed and slip.
- Change PWM frequency from 2 kHz to 12 kHz.
- Observe how the switching pattern changes.
- Enable different harmonic components.
- Try the fault demonstrations.