Interactive Harmonic Resonance Simulation

⚡ Harmonic Resonance Simulation

Demonstration of resonance between harmonic frequency and an LC system natural frequency

1. Simulation Controls

50 Hz
250 Hz
0.20
5%
System is away from resonance

2. Electrical System

AC Supply
50 Hz
→
Harmonic
Source
→
System
Inductance L
→
PFC Capacitor
C
→
Load

The electrical system contains inductance and capacitance. Together they can form a resonant circuit. When the frequency of a harmonic approaches the natural frequency of this LC system, the harmonic component can be strongly amplified.

3. Resonance Calculation

Harmonic Frequency
250 Hz
Natural Frequency
250 Hz
Frequency Difference
0 Hz
Amplification
26×
Relative Harmonic Current
130%

4. Oscilloscope — Voltage and Current

The upper waveform represents the harmonic voltage. The lower waveform represents the resulting harmonic current. Near resonance, the current amplitude increases dramatically.

5. Resonance Curve

The vertical axis represents relative amplification. The peak occurs when the harmonic frequency approaches the natural resonant frequency.

⚠ What Happens During Harmonic Resonance?

  • Harmonic current can become greatly amplified.
  • Capacitors may experience excessive current and heating.
  • Harmonic voltage can increase substantially.
  • Transformers can experience additional heating and losses.
  • Motors can experience torque pulsation, vibration and heating.
  • Protective devices may experience nuisance tripping.
  • Severe resonance can contribute to equipment failure.

🛠 Resonance Mitigation

The Apply Detuned Filter button shifts the effective resonant frequency away from the selected harmonic. This demonstrates the basic principle of using reactors and detuned capacitor banks to reduce resonance risk.

  • Detuned capacitor banks
  • Series reactors
  • Passive harmonic filters
  • Active harmonic filters
  • Appropriate system impedance management
  • Properly designed capacitor-bank installations

6. Learning Experiment

  1. Select the 5th harmonic.
  2. Set the fundamental frequency to 50 Hz.
  3. The 5th harmonic becomes 250 Hz.
  4. Set the natural resonant frequency to approximately 250 Hz.
  5. Observe the resonance indicator.
  6. Watch the current waveform increase.
  7. Move the resonant frequency away from 250 Hz.
  8. Observe the reduction in amplification.
  9. Press Apply Detuned Filter and observe the change.
```